Intrinsically Safe vs Non-Incendive: What Is the Difference?

Intrinsically safe equipment limits electrical and thermal energy so it cannot ignite a hazardous atmosphere even when faults occur, which allows use in the most hazardous areas. Non-incendive equipment cannot cause ignition in normal operation, but is not protected against faults, so it is limited to Division 2 or Zone 2 areas.

01

The Short Answer

Intrinsic safety works by keeping energy too low to ignite anything, which suits low-power devices such as sensors and handheld radios. A panel PC with a large screen and an Intel Core processor draws too much power for that, so most hazardous area HMIs are non-incendive designs certified for Division 2 or Zone 2.

  • //
    Check the area first Division 1 or Zone 0/1 rules out non-incendive equipment.
  • //
    Match the power High-power computers are rarely intrinsically safe; low-power instruments often are.
  • //
    Look at the marking Ex ia or ib marks intrinsic safety for Zones 0 and 1; Ex ic is for Zone 2.
  • //
    Mind the wiring Intrinsically safe circuits need barriers or isolators back to the safe area.