What a rack unit measures
A rack unit is the unit of height used for equipment that mounts in a standard 19 inch (19″) rack. One rack unit, written 1U or sometimes 1RU, is 1.75 inches, or 44.45 mm. Equipment heights are always whole or half multiples of it, so a 1U server, a 2U storage chassis and a 4U GPU system all fit the same rails and stack without gaps.
The dimension comes from the EIA-310 standard in the US and the equivalent IEC 60297 internationally. Both fix the 19 inch panel width and the 1.75 inch vertical pitch, which is why equipment from different manufacturers fits the same rack.
A front panel is made very slightly shorter than its nominal height, typically by about 1/32 inch (0.8 mm), so that a 1U panel measures around 43.7 mm. The small gap lets neighbouring equipment be fitted and removed without binding.
Rack unit to inches and millimetres
Converting is simple: multiply the number of U by 1.75 for inches or by 44.45 for millimetres. The table shows common heights for equipment and for whole racks.
| Height | Inches | Millimetres | Typical use |
|---|---|---|---|
| 1U | 1.75 | 44.45 | Network switches, KVM console drawers, compact servers |
| 2U | 3.5 | 88.9 | Servers with full-height expansion cards or more drives |
| 3U | 5.25 | 133.35 | Storage and GPU servers, industrial chassis |
| 4U | 7 | 177.8 | Multi-GPU servers, rack-mount PCs with many slots |
| 6U | 10.5 | 266.7 | Small wall-mount cabinets |
| 12U | 21 | 533.4 | Wall-mount and floor-standing cabinets |
| 24U | 42 | 1,066.8 | Half-height racks for offices and control rooms |
| 42U | 73.5 | 1,866.9 | Full-height data centre racks |
The rack heights are the usable mounting space. The finished cabinet is taller, because the frame, top and plinth add to it: a 42U cabinet usually stands about 2 m high. Rack-mount monitors and panel PCs also take a whole number of U, which the datasheet states.
What is a 19 inch rack?
A 19 inch rack is the standard frame or cabinet for mounting servers, network switches, monitors, power supplies and other equipment, named after the 19 inch (482.6 mm) width of the front panels it takes. The format comes from telephone exchanges: AT&T standardised panels of that width on a 1.75 inch height step in the early 1920s, and the same dimensions carried over into broadcast, test and measurement, and later data-centre equipment. Today they are defined by EIA-310-E in the US and IEC 60297-3-100 internationally, which is why a 19 inch chassis from one maker fits a rack from another.
| Dimension | Inches | Millimetres | Notes |
|---|---|---|---|
| Front panel width | 19 | 482.6 | Includes the mounting ears |
| Opening between the posts | 17.75 | 450 | Sets the maximum chassis width |
| Mounting hole centres, left to right | About 18.3 | About 465 | Lines up with the slots in the panel ears |
| Height of 1U | 1.75 | 44.45 | Three mounting holes per U on each post |
| Cabinet outside width | About 23.6 or 31.5 | 600 or 800 | Wider cabinets leave room for cabling at the sides |
| Cabinet depth | About 23.6–47.2 | 600–1,200 | Not fixed by the standard |
| Full-height 42U cabinet | About 79 | About 2,000 | 73.5 inches (1,866.9 mm) of mounting space |
The 19 inch figure is the width of the equipment, not of the rack. Racks come as open two-post and four-post frames, enclosed cabinets with doors and side panels, wall-mount cabinets, and transit cases with internal shock mounts for vehicles and field use, and all of them take the same 19 inch equipment. In telecoms you may also meet the 23 inch rack, which keeps the same rack unit but takes wider panels, so 19 inch equipment needs adapter brackets to fit it.
Much industrial equipment is built to the format too, from rack mount panel PCs for operator consoles to rack mount industrial Ethernet switches for control and substation networks.
How the 19 inch rack is laid out
Each rack unit has three mounting holes on each vertical rail. The holes are not evenly spaced: the pattern repeats at 0.625, 0.625 and 0.5 inches (15.875, 15.875 and 12.7 mm), so the closer pair marks the boundary between one U and the next. Many racks print U numbers on the rails to make counting easier, and it is good practice to record each item’s position by its lowest U so equipment can be found and replaced quickly.
-
//
Panel width. The front panel, including its mounting ears, is 19 inches (482.6 mm) wide. The opening between the rails is about 17.75 inches (450 mm), which sets the maximum chassis width.
-
//
Square or threaded holes. Most server racks have square holes that take cage nuts, typically M6. Older and telecom racks often have round threaded holes for 10-32 or 12-24 screws.
-
//
Two-post or four-post. Two-post racks hold light equipment such as switches and patch panels by the front ears. Servers need four-post racks or enclosed cabinets so rails can support them front and back.
-
//
Rails and shelves. Heavier equipment rides on slide rails so it can be pulled forward for service without removing it from the rack. Lighter items without rail kits sit on fixed shelves, which themselves take one or more U of space.
-
//
Depth. Depth is not standardised. Cabinets are commonly 600, 800, 1,000 or 1,200 mm deep, and short-depth chassis suit shallow wall-mount, telecom and control cabinets.
Other rack formats
The 19 inch rack is by far the most common, but you may meet a few others. Ten-inch racks are half-width versions for small networks and keep the same 1.75 inch rack unit. ETSI racks used in European telecoms are 535 mm wide and count height in 25 mm steps. The Open Compute Project’s Open Rack uses a 21 inch equipment width and its own 48 mm OpenU. Equipment for one format does not fit another without adapters, so check the rack before choosing the chassis.
Planning rack space for industrial systems
Counting U is only the start. Power distribution, cooling and weight usually limit a rack before space does. Most rack equipment draws cool air in at the front and exhausts it at the back, so fill unused U with blanking panels to stop hot air circulating back to the front. Leave spare U for cable management and growth, and put the heaviest equipment at the bottom. In factories and substations, check the rack’s depth and the ambient temperature as well, since control-room and cabinet racks are often shallower and warmer than data-centre ones.
Our rack mount servers cover the common heights, from the Premio LLM-1U-RPL 1U edge AI servers to the Premio LLM-2U-AM5 2U server and Premio LLM-3U-AM5 3U server with room for full-height GPU cards. For the operator’s view, 19 inch rack mount monitors fit the same rails, and our rack mount KVM consoles fold a screen and keyboard into a 1U drawer.
Quick answers on the rack unit
Rack unit: common questions
How tall is 1U?
1.75 inches, or 44.45 mm. That is the nominal height. Front panels are made about 0.8 mm shorter so that neighbouring equipment does not bind.
What does 2U mean?
Twice the height of 1U: 3.5 inches or 88.9 mm. A 2U chassis has room for full-height expansion cards and more drive bays than a 1U one.
How many U are in a standard rack?
Usually 42U for a full-height rack. Taller 45U, 47U and 48U racks are also common, and wall-mount cabinets typically range from about 6U to 15U.
What does RU stand for?
Rack unit. RU and U mean the same thing. Some datasheets write 1RU or 2RU instead of 1U or 2U.
Does the rack unit set the width or depth?
No, only the height. Width is fixed by the 19 inch standard, and depth varies by rack and by equipment, so always compare the chassis depth with the cabinet.
What size is a 19 inch rack cabinet?
Usually 600 or 800 mm wide and 600 to 1,200 mm deep. The 19 inch figure is the width of the equipment it holds, and a full-height 42U cabinet stands about 2 m tall.