The core difference
Intrinsically safe equipment limits electrical and thermal energy so it cannot ignite a hazardous atmosphere even when faults occur, which allows use in the most hazardous areas. Non-incendive equipment cannot cause ignition in normal operation, but is not protected against faults, so it is limited to Division 2 or Zone 2 areas.
Both are ways of making electrical equipment safe where flammable gas, vapor or dust may be present. Neither relies on a heavy enclosure to contain an explosion, which is what explosion-proof or flameproof designs do. The difference is how many things are allowed to go wrong: intrinsic safety assumes components can fail, while non-incendive design assumes the equipment is working as intended.
Intrinsic safety works by keeping energy too low to ignite anything, which suits low-power devices such as sensors and handheld radios. A panel PC with a large screen and an Intel Core processor draws too much power for that, so most hazardous area HMIs are non-incendive designs certified for Division 2 or Zone 2.
How intrinsic safety works
An intrinsically safe circuit is designed so that the energy available at any point, including in a spark when a wire breaks or shorts, stays below what is needed to ignite the gas. Stored energy in capacitors and inductors is limited too, and surface temperatures are kept below the temperature class.
Where an intrinsically safe field device connects to equipment in the safe area, a zener barrier or galvanic isolator sits between them and caps the voltage and current that can reach the hazardous area. Engineers check each loop with entity parameters: the maximum voltage, current, power, capacitance and inductance the device can accept against what the barrier can deliver. The international standard is IEC 60079-11, and in the US UL 913.
-
//
Level ia. Stays safe with two independent faults. Suitable for Zone 0, 1 and 2, and for Class I, Division 1.
-
//
Level ib. Stays safe with one fault. Suitable for Zone 1 and 2.
-
//
Level ic. Safe in normal operation, the IEC equivalent of non-incendive. Suitable for Zone 2 only.
How non-incendive equipment works
Non-incendive equipment, written nonincendive in US standards, is designed so that nothing in it can produce an igniting spark or hot surface while it is operating normally. Contacts that open and close are sealed or kept at low energy, and surface temperatures are controlled. The US standard is UL 121201, formerly ISA 12.12.01, and the IEC zone system uses comparable concepts such as Ex ec and Ex ic.
Because faults are not covered, non-incendive equipment relies on the area itself being safe most of the time. That is exactly the definition of Division 2 and Zone 2: a flammable atmosphere only appears if something else fails, and the chance of that coinciding with a fault in the equipment is accepted as very low.
A related idea is nonincendive field wiring. Here the equipment in the safe area or the Division 2 area limits the energy on a particular circuit, such as a sensor loop, so that opening, shorting or earthing that wiring in normal operation cannot ignite the atmosphere. That lets the field wiring use ordinary Division 2 methods without barriers, while the rest of the equipment stays non-incendive.
Intrinsically safe and non-incendive compared
| Aspect | Intrinsically safe | Non-incendive |
|---|---|---|
| Principle | Energy too low to ignite, even under faults | No igniting sparks or hot surfaces in normal operation |
| Faults considered | One (ib) or two (ia) | None |
| Permitted areas | Division 1 and 2; Zones 0, 1 and 2 (by level) | Division 2 and Zone 2 only |
| Power available | Very low, typically a few watts or less | Normal equipment power |
| Wiring | Barriers or isolators, segregated IS cabling | Nonincendive field wiring rules or standard Division 2 methods |
| Standards | IEC 60079-11, UL 913 | UL 121201, IEC 60079-7 (Ex ec), IEC 60079-11 (Ex ic) |
| Typical equipment | Sensors, transmitters, radios, handhelds | Panel PCs, HMIs, monitors, lighting, controllers |
In short, intrinsic safety buys access to the most hazardous areas at the cost of very low power. Non-incendive design keeps normal power but is limited to areas where the hazard is occasional.
Choosing between them
The area classification usually makes the decision before the equipment does.
-
//
Check the area first. Division 1 or Zone 0/1 rules out non-incendive equipment.
-
//
Match the power. High-power computers are rarely intrinsically safe; low-power instruments often are.
-
//
Look at the marking. Ex ia or ib marks intrinsic safety for Zones 0 and 1; Ex ic is for Zone 2.
-
//
Mind the wiring. Intrinsically safe circuits need barriers or isolators back to the safe area.
-
//
Consider the alternatives. Where a full computer must sit in Division 1 or Zone 1, purged or flameproof enclosures are the usual route. Our ATEX zones explainer shows which zones need which category.
Quick answers on intrinsically safe vs non-incendive
Intrinsic safety and non-incendive: common questions
What does intrinsically safe mean?
Unable to ignite the atmosphere, even with faults. The circuit energy is limited so that neither sparks nor hot surfaces can cause ignition, even when components fail.
Is non-incendive the same as explosion proof?
No. Explosion-proof equipment contains an internal explosion in a strong enclosure. Non-incendive equipment avoids ignition sources in normal operation instead.
Can non-incendive equipment be used in Division 1?
No. It is only permitted in Division 2 and Zone 2, where a flammable atmosphere is not expected in normal operation.
Are iPhones intrinsically safe?
No. Standard smartphones and tablets are not certified for hazardous areas. Specialist intrinsically safe phones and tablets exist for that purpose.
Is intrinsically safe better than non-incendive?
Safer, not always better. Intrinsic safety covers harsher areas, but its power limits rule out most full computers, so non-incendive is often the practical choice for Zone 2 HMIs.