What Class 1 Division 2 means
Class 1 Division 2, usually written Class I, Division 2 in the codes and C1D2 for short, is a hazardous location rating used in the United States and Canada. Class I means flammable gases or vapours may be present. Division 2 means they are not expected in normal operation, and would only appear under abnormal conditions such as a leak, a failed seal or a ventilation fault.
The system comes from the US National Electrical Code (NEC), Article 500 onwards, and the Canadian Electrical Code. Equipment rated for Class I, Division 2 will not ignite the surrounding atmosphere in normal operation. It is the most common hazardous location rating for computers, HMIs and displays, because it covers the large areas around process plant rather than the inside of tanks and vents.
Classes, divisions and groups
A full hazardous location rating has three parts: the class (what kind of material), the division (how likely it is to be present) and the group (which specific material).
-
//
Class I. Flammable gases, vapours and mists, such as natural gas, propane, hydrogen and solvent vapor.
-
//
Class II. Combustible dust, split into groups E (metal dust), F (carbon dust) and G (grain, flour, wood and plastic dust).
-
//
Class III. Easily ignitable fibers and flyings, such as cotton lint and sawdust, which are too heavy to stay in the air.
-
//
Groups A to D. The Class I gas groups, from acetylene (A) and hydrogen (B) to ethylene (C) and propane (D). Equipment rated for all four suits the widest range of gases.
-
//
Temperature code. A T code from T1 to T6 gives the maximum surface temperature, which must sit below the ignition temperature of the gas on site.
Division 1 vs Division 2
The division is the part buyers most often get wrong, and it decides how the equipment must be protected.
| Aspect | Division 1 | Division 2 |
|---|---|---|
| Hazard present | In normal operation, or often during repair or maintenance | Only under abnormal conditions such as a leak or failure |
| Typical location | Inside vents, open filling points, pits where gas collects | Around flanges, valves and pumps; next to a Division 1 area |
| Protection methods | Explosion proof, intrinsically safe, purged Type X or Y | Nonincendive, non-sparking, purged Type Z, hermetically sealed, plus all Division 1 methods |
| Typical computers and HMIs | Rare; usually purged or explosion-proof enclosures | Common; most hazardous location panel PCs are rated here |
| Nearest zone equivalent | Zone 0 and Zone 1 | Zone 2 |
| Wiring | Rigid conduit and sealing fittings in most cases | Wider choice of wiring methods under the NEC |
Equipment rated for Division 1 can be used in Division 2, but not the other way round. Many Division 2 products are also rated for groups A to D and a specific T code, which should appear on the nameplate alongside the class and division.
What is Class 1 Division 1?
Class I, Division 1 is the stricter of the two gas divisions. Under NEC Article 500 it covers locations where ignitable concentrations of flammable gas or vapor exist under normal operating conditions, exist often because of repair, maintenance or leakage, or could be released by a breakdown that also causes an electrical fault. Typical examples are the inside of spray booths, the area around open dip tanks and filling points, and pits or sumps where heavy vapours collect.
Because the hazard is expected rather than occasional, Division 1 equipment must stay safe even if the atmosphere is present while it runs. That rules out the nonincendive designs used in Division 2 and leaves three main methods:
-
//
Explosion proof (XP). An enclosure strong enough to contain an internal explosion and cool the escaping gases, listed to standards such as UL 1203, with threaded conduit and sealing fittings.
-
//
Intrinsically safe (IS). Circuits limited to energy levels that cannot ignite the gas even with faults, listed to UL 913. The usual choice for sensors, transmitters, radios and handheld meters.
-
//
Purged and pressurised (Type X and Type Y). Under NFPA 496, Type X purging reduces the inside of an enclosure from Division 1 to unclassified, and Type Y from Division 1 to Division 2. This is the common route when a full computer or display must sit in a Division 1 area.
Computers in Division 1 and Division 2 areas
Full computers rarely go into Division 1. The usual design keeps the computer in a Division 2 or unclassified area and brings the field signals to it through intrinsically safe barriers, or houses it in a purged cabinet. Division 2 is where most hazardous location computers, displays and network switches are listed, and that is the area our catalog covers.
Our rugged tablets include a 10.1 inch model listed for Class I, Division 2, Groups A, B, C and D, T4, alongside ATEX and IECEx Zone 2, and several of our managed industrial switches list UL Class 1 Division 2 approval for control cabinets in classified areas. None of these are rated for Division 1.
How C1D2 equipment is certified
In the US, hazardous location equipment is tested and listed by a Nationally Recognized Testing Laboratory (NRTL) such as UL, CSA, FM Approvals or Intertek. For computers and HMIs, the usual standard for Division 2 is UL 121201 (formerly ISA 12.12.01), which covers nonincendive electrical equipment. In Canada, the equivalent is CSA C22.2 No. 213.
The listing appears on the nameplate, for example “Class I, Division 2, Groups A, B, C, D, T4”. Our guide to UL listed computers for control panel builders explains how listings work more generally.
Choosing a computer for a C1D2 area
A Division 2 listing is the starting point, not the whole specification. Check these points against the area classification drawing before ordering.
-
//
Groups and T code. Confirm the listing covers the gas groups on site and that the T code sits below the ignition temperature of every gas present.
-
//
Ambient temperature. Hazardous location listings state an ambient range. Outdoor or sun-exposed installs may need a wider range than the default.
-
//
Connections and accessories. Cables, USB devices and add-on cards can break the listing. Use only the connections and accessories the certificate allows.
-
//
Ingress protection. Many C1D2 sites are also wet or washed down, so check the IP or NEMA rating as well as the hazardous location rating.
-
//
Both markings for global sites. If the same design must go to Europe or the Middle East, choose a product that also carries ATEX or IECEx Zone 2 marking.
How C1D2 compares with ATEX zones
Europe and much of the rest of the world use zones under ATEX and IECEx rather than divisions. Division 1 covers what the zone system splits into Zone 0 and Zone 1, while Division 2 broadly matches Zone 2. Our ATEX zones explainer sets out each zone.
-
//
Separate certification. C1D2 and ATEX are separate approvals; one does not imply the other. Products sold into both markets often carry both markings.
-
//
Zones in the US too. The NEC also allows a zone system in Articles 505 and 506, which many international projects use to keep one design across sites.
-
//
C1D2 rooms. In cannabis and botanical extraction, a C1D2 room is a ventilated, gas-monitored space built so that solvent leaks stay at Division 2 conditions.
Quick answers on Class 1 Division 2
Class 1 Division 2: common questions
Is Class 1 Division 2 explosion proof?
No. Explosion proof is one protection method, normally used for Division 1. Division 2 equipment is usually nonincendive or non-sparking instead.
Does Class 1 Div 2 require explosion-proof equipment?
No. The NEC permits nonincendive, non-sparking, purged Type Z and hermetically sealed equipment in Division 2, so explosion-proof enclosures are not needed.
What is the difference between Class 1 Div 1 and Div 2?
How often gas is present. Division 1 has a flammable atmosphere in normal operation; Division 2 only under abnormal conditions, so its equipment rules are less strict.
What does C1D2 mean?
Class I, Division 2. It is shorthand for a location where flammable gas or vapor is only expected if something goes wrong.
Is Class 1 Division 2 the same as ATEX Zone 2?
Similar, but not the same. The hazards are comparable, but the two are certified separately and use different markings.
What is Class 1 Division 1?
Where flammable gas is present in normal operation. Class I, Division 1 covers locations where ignitable gas or vapor exists during normal operation, repair or maintenance, so only explosion-proof, intrinsically safe or purged equipment is allowed.